Hybrid control scheme for the current loop of a grid connected inverter operating with highly distorted grid voltage

Julio Viola, Jose Restrepo, Jose Manuel Aller, Flavio Quizhpi

Producción científica: Contribución a una conferenciaDocumento

1 Cita (Scopus)

Resumen

© 2016 IEEE. The complete design of the current control loop for single-phase inverters connected to weak grids is presented. The problems associated to the design of current control loop when highly distorted grid voltages are present and LCL filters are used to couple the inverters to the grid, are analyzed. Fourier coefficients decomposition is used to obtain an ahead-of-time version for the nonideal voltage signal which allows the compensation of the current control loop delay. Also the relevance of nonideal characteristic of the inverter as the dead-time effect on the shape of the controlled current is analyzed and compensated. Simulations and experimental results are included for the proposed methods.
Idioma originalInglés
DOI
EstadoPublicada - 1 ene. 2016
EventoIEEE Energy Conversion Congress and Exposition, Proceedings - Milwaukee, Estados Unidos
Duración: 18 sep. 201622 sep. 2016

Conferencia

ConferenciaIEEE Energy Conversion Congress and Exposition, Proceedings
Título abreviadoECCE 2016
País/TerritorioEstados Unidos
CiudadMilwaukee
Período18/09/1622/09/16

Huella

Profundice en los temas de investigación de 'Hybrid control scheme for the current loop of a grid connected inverter operating with highly distorted grid voltage'. En conjunto forman una huella única.

Citar esto