Skip to main navigation Skip to search Skip to main content

Protection settings in a distribution system with a medium voltage motor as load

Research output: Chapter in Book/Report/Conference proceedingConference contributionpeer-review

Abstract

Due to the constant growth of the industrial sector and the use of high capacity electric motors, there was a need to implement protection setting criteria for motors coupled to medium voltage networks. The article presents the implementation of three overcurrent IEDs, one for distance and one for motor protection in an electrical system that starts from a subtransmission line with a real data network equivalent. The electrical system and the settings of the protections were simulated in the PowerFactory software. To validate the proposed settings and injection of fault voltages and currents in the IEDs, the Omicron CMC356 test equipment is used. The response times between the simulation and the physical response of the IED vary by ± 10 ms, which validates the proposed methodology. Setting and coordination criteria that can be implemented in sub-transmission, distribution, and motor protection electrical networks are presented and validated.

Original languageEnglish
Title of host publication2024 3rd International Conference on Power Systems and Electrical Technology, PSET 2024
PublisherInstitute of Electrical and Electronics Engineers Inc.
Pages568-575
Number of pages8
ISBN (Electronic)9798350353204
DOIs
StatePublished - 2024
Event3rd International Conference on Power Systems and Electrical Technology, PSET 2024 - Tokyo, Japan
Duration: 5 Aug 20248 Aug 2024

Publication series

Name2024 3rd International Conference on Power Systems and Electrical Technology, PSET 2024

Conference

Conference3rd International Conference on Power Systems and Electrical Technology, PSET 2024
Country/TerritoryJapan
CityTokyo
Period5/08/248/08/24

Bibliographical note

Publisher Copyright:
© 2024 IEEE.

UN SDGs

This output contributes to the following UN Sustainable Development Goals (SDGs)

  1. SDG 7 - Affordable and Clean Energy
    SDG 7 Affordable and Clean Energy

Keywords

  • Commissioning tool
  • IED
  • Motor Protection
  • Relay protection
  • Transformer Protection

Fingerprint

Dive into the research topics of 'Protection settings in a distribution system with a medium voltage motor as load'. Together they form a unique fingerprint.

Cite this